Insulation resistance test: what it is and what reading is OK

Updated: 2026-10-26

For 230/400 V installations to IEC standards (Europe, UK and most of the world). North America uses different voltages, colours and rules: see the “Around the world” notes.

An insulation resistance test checks whether cable insulation is leaking current. The tester applies a DC voltage (usually 500 V DC for 230/400 V circuits) and measures resistance between conductors and between each conductor and PE. The minimum for a domestic installation is 1 MΩ; a healthy, dry installation typically reads tens or hundreds of MΩ.

Why it is done

Insulation ages. It can be scuffed on a sharp edge, scorched or damp. Damaged insulation means leakage current, a shock risk and a fire risk. This test finds those faults before they cause harm, even where you cannot see them: inside the wall.

How the test is done

  • The circuit is isolated from the supply, and sensitive equipment (electronics, LED drivers, power supplies) and surge protectors are disconnected. Otherwise they lower the reading or get damaged.
  • The insulation tester (often called a "megger") applies a test voltage: 500 V DC for ordinary 230/400 V circuits.
  • Measurements are taken L-N, L-PE and N-PE (on three-phase, between all conductors).

Test voltage and minimum reading

Values from IEC 60364-6 (adopted in Europe as HD 60364-6):

Circuit nominal voltage Test voltage (DC) Minimum insulation resistance
up to 50 V (SELV and PELV) 250 V 0.5 MΩ
above 50 V up to 500 V (normal 230/400 V circuits) 500 V 1 MΩ
above 500 V 1000 V 1 MΩ

If surge protectors cannot be disconnected, the test voltage may be reduced to 250 V, but the result must still be at least 1 MΩ.

What good looks like in practice

Reading Verdict
below 1 MΩ too low: find the fault
1 to 10 MΩ acceptable, but keep an eye on it
tens to hundreds of MΩ healthy, dry installation

When a whole installation reads too low, it is split into groups of circuits and each is tested separately to find the weak one. A low reading on one circuit usually means a damp box, a damaged cable or an appliance someone forgot to disconnect.

When it is done

On initial verification of a new installation, after major alterations, and during periodic inspections. The result goes into the test certificate.

Around the world:
• UK: BS 7671 uses the same values (500 V test, 1 MΩ minimum for 230/400 V circuits) and records them on the Electrical Installation Certificate or EICR.
• USA: the NEC does not set a general minimum for building wiring; insulation testing is mainly specified by equipment standards and maintenance practice.
Important: insulation resistance testing is done by a qualified person with a calibrated instrument. 500 V DC can damage connected equipment and give a nasty shock. This page explains the test; it does not replace it.