Insulation resistance test: what it is and what reading is OK
Updated: 2026-10-26
For 230/400 V installations to IEC standards (Europe, UK and most of the world). North America uses different voltages, colours and rules: see the “Around the world” notes.
Why it is done
Insulation ages. It can be scuffed on a sharp edge, scorched or damp. Damaged insulation means leakage current, a shock risk and a fire risk. This test finds those faults before they cause harm, even where you cannot see them: inside the wall.
How the test is done
- The circuit is isolated from the supply, and sensitive equipment (electronics, LED drivers, power supplies) and surge protectors are disconnected. Otherwise they lower the reading or get damaged.
- The insulation tester (often called a "megger") applies a test voltage: 500 V DC for ordinary 230/400 V circuits.
- Measurements are taken L-N, L-PE and N-PE (on three-phase, between all conductors).
Test voltage and minimum reading
Values from IEC 60364-6 (adopted in Europe as HD 60364-6):
| Circuit nominal voltage | Test voltage (DC) | Minimum insulation resistance |
|---|---|---|
| up to 50 V (SELV and PELV) | 250 V | 0.5 MΩ |
| above 50 V up to 500 V (normal 230/400 V circuits) | 500 V | 1 MΩ |
| above 500 V | 1000 V | 1 MΩ |
If surge protectors cannot be disconnected, the test voltage may be reduced to 250 V, but the result must still be at least 1 MΩ.
What good looks like in practice
| Reading | Verdict |
|---|---|
| below 1 MΩ | too low: find the fault |
| 1 to 10 MΩ | acceptable, but keep an eye on it |
| tens to hundreds of MΩ | healthy, dry installation |
When a whole installation reads too low, it is split into groups of circuits and each is tested separately to find the weak one. A low reading on one circuit usually means a damp box, a damaged cable or an appliance someone forgot to disconnect.
When it is done
On initial verification of a new installation, after major alterations, and during periodic inspections. The result goes into the test certificate.
• UK: BS 7671 uses the same values (500 V test, 1 MΩ minimum for 230/400 V circuits) and records them on the Electrical Installation Certificate or EICR.
• USA: the NEC does not set a general minimum for building wiring; insulation testing is mainly specified by equipment standards and maintenance practice.